Previous Page  10 / 152 Next Page
Information
Show Menu
Previous Page 10 / 152 Next Page
Page Background

LK 810 ThermoMat 2.0 G is a loading unit for heating applications

with solid fuel boilers and storage tanks. The loading unit is intended

to ensure a high return temperature as well as an optimal temperature

stratification in the storage tank, thus increasing the efficiency of the

system. Tarring and condensation are prevented which prolongs boiler

life.

The LK 810 ThermoMat 2.0 G is a compact design with an integra-

ted low-energy circulating pump, that fulfills the requirements of ErP

2015, and a thermic loading valve that regulates on two ports. The

loading unit has three ball valves to simplify installation and main-

tenance, three thermometers that allow for simple control of the lo-

ading process and an insulation to minimize heat loss. The loading unit is

available in two versions - with or without check valve. With a check

valve the functions described under phase 4 will be obtained.

LK 810 ThermoMat 2.0 G is also available with a circulating pump that

is controlled by a PWM-signal. For more information please contact

our sales department.

LK 810 ThermoMat 2.0 G is installed in the return circuit between

the solid fuel boiler and the storage tank. The unit should be mounted

upright with the drive-shaft of the circulating pump in a horizontal

position. The loading unit is reversible and can easily be adapted for

mounting to the right or left of the boiler.

The loading unit normally requires no maintenance. The installation

should be checked regularly. Thanks to the three ball valves any part

can be changed without draining the system in case of servicing.

Voltage

230 VAC 50 Hz

Power consumption

Max. 52 W

Max. boiler efficiency

65 kW at 20°C ΔT

Return temperature

55°C, 60°C, 65°C or 70°C

Working temperature

Min. +5°C/Max. +110°C

Ambient temp.

Min. +0°C/Max. +70°C

Max. working pressure

1,0 MPa (10 bar)

Media

Water - Glycol mixture max. 50%

Thread standard

Rp - female thread

Circulating pumps

Grundfos UPM3 AUTO L xx-70

Material, valve body

Brass EN 1982 CB753S

Material, insulation

Expanded Polypropylene EPP

TECHNICAL DATA

The function of the loading unit during the

different phases of heating:

1. HEAT UP PHASE

The water circulates between boiler and

loading unit while the temperature of the

boiler is rising.

2. LOADING PHASE

The thermostatic element starts to open and

allows return water from the storage tank to

be mixed with supply water before it returns

to the boiler. The return temperature to the

boiler is kept constant.

3. END PHASE

The thermostatic element is fully open and

the bypass is closed. This results in an opti-

mal transfer of heat from the boiler and the

storage tank is filled with supply water.

4. SELF-CIRCULATIONWITH CHECKVALVE

Self-circulation will be obtained as soon

as the fire has gone out and the circulating

pump has stopped. The remaining hot water

is loaded to the storage tank. In case of power

failure or pump breakdown the check valve

automatically opens to allow self-circulation.

The check valve also stops recirculation from

storage tank to boiler.

Loading Units | LK 810 ThermoMat 2.0 G

10

LK 810 ThermoMat 2.0 G